QSE Logo

LetsTalk2015@QSEng.com
612.308.4716

Commissioning: Art Storage Vault Air Handling Unit Trend Analysis

This is the third in a series of columns in which I demonstrate examples of systems performance information that can be gleaned from trend log analysis. In these columns I introduce a system or sub-system; show a trend graph; and then leave it up to the reader to discover the operational “issue” illustrated in the graph. The answer will be given at the start of the subsequent month’s column.

November 2011 Trend Log Analysis

Last month’s trend graph was for an air handling unit serving a space with extremely tight temperature and relative humidity requirements. The first thing that was clear from the trend graph was that the space conditions were very steady. The return air temperature appeared to be a constant 71°F with less than a ±1°F variance. Similarly, the return air relative humidity was a steady 50% RH with less than a ±2% RH variance.

The next most noticeable thing about the graph is how solid the colors are, indicating continuous movement of the control devices (chilled water valve, hot water valve, and humidifier). This meant that there was essentially simultaneous cooling/dehumidification, heating, and humidification.

Although we might expect simultaneous cooling/dehumidification and reheating for summertime space humidity control, it was surprising to see the humidifier continuously modulating between 0-30% open. There should have been no need to mechanically humidify during the month of August. We believe that the humidification control loop (controlling the humidifier) and the dehumidification control loop (controlling the chilled water valve) were both controlling to a 50% RH setpoint and both loops were not tuned very well. As the return air relative humidity rose slightly above 50% RH, the humidifier valve closed while the chilled water valve opened nearly fully. This resulted in the return air relative humidity quickly dropping below 50% RH, causing the chilled water valve to back off and the humidifier to modulate open. This cycle repeated itself multiple times each hour.

This wild modulation of control devices was not only hard on the physical devices; it used more energy than necessary. Programming a slight deadband between humidification and dehumidification (i.e., control humidification for 49% RH and dehumidification for 51% RH) and fine tuning the control loops could have eliminated the need for any steam in the summertime. It could have also eliminated the overcooling of the supply air and the associated need for more reheat than necessary.

New System

The following graph illustrates an air handling unit serving a museum’s art storage vault in a northern climate. The vault is located below grade and is typically unoccupied and dark. The environmental control criteria are tight, with art conservators expecting 70°F and 40-50% RH year round. This is a constant volume, single zone system with a mixing box, chilled water coil, heating hot water reheat coil, humidifier, and supply fan. There is no airside economizer but only a constant minimum outside air damper to maintain a slightly positive space pressure. This trend analysis was conducted as part of a facility-wide retro-commissioning program, not because there were any known problems with this system.

Trends

The building automation system was used to trend the following sensor and device data at fifteen minute intervals:

  • Mixed air temperature (yellow)

  • Discharge air temperature (purple)

  • Space temperature (blue)

  • Chilled water valve signal (green)

  • Heating hot water valve signal (orange)

  • Heating coil pump status (red)

The following graph covers about 10 days in the fall of 2006.

AHU Trend Log

 

Commissioning: Getting It Right

Engineered Systems, December 2011

by
Rebecca Ellis, PE, LEED AP BD+C, CCP, CPMP, CxA
President
Questions & Solutions Engineering
1079 Falls Curve
Chaska, MN  55318
rteesmag@QSEng.com